Error codes during pcp communication – Burkert Type 8644 User Manual
Page 87
8644/phoenix - 83
S
YSTEM
D
ESCRIPTION
Error codes during PCP communication
State conflict
Coding
05h / 01h
Relevance
A start or stop command was sent twice.
Cause
Error only occurs during the start or stop service:
Since start or stop has already been carried out, the service cannot be carried out
again.
Resolution
No action necessary.
Hardware fault
Coding
06h / 02h
Relevance
Access to the object failed due to a hardware fault.
Cause
e.g. no peripheral voltage
Resolution
Remedy the fault.
Object Access Denied
Coding
06h / 03h
Relevance
The object has restricted access rights.
Cause
The object may only be able to be read but is not writable, or it is password protected.
Resolution
Check the access rights in the object description.
Object Attribute Inconsistent
Coding
06h / 05h
Relevance
A service parameter was given with an impermissible value.
Cause
e.g. an incorrect length indication or an impermissible sub-index
Resolution
Check the parameters on the basis of the object description and re-set the service with
the corrected values.
Object Access Unsupported
Coding
06h / 06h
Relevance
The service used cannot be applied to this object.
Cause
e.g. a program sequence can be started or stopped, but not read.
Resolution
Check which services are permitted for this object in the object description.