Product description

5.4.2 Device versions

actuator sizes
Depending on the orifice, the globe control valve is available for the
following actuator sizes:

Orifice dn

available actuator size ø [mm]

4 - 15

50

70

-

-

20

50

70

25

50

70

90

32

-

90

130

40

90

130

50

90

130

65

-

130

80

130

100

130

Tab. 1: Actuator sizes

pilot pressure
Designs with lower pilot pressure (reduced spring force) are
available on request.
Contact your Bürkert sales office or our Sales Centre.
E-mail: [email protected]

5.5

Designated application area

Observe the maximum pressure range according to the
type label!

• Neutral gases and liquids up to 16 bar.
• Steam up to 11 bar absolute / 185 °C for seat seal steel / steel.

Steam up to 2.7 bar absolute / 130 °C for seat seal PTFE / steel.

• Aggressive media.

5.5.1 application areas

e.g.

Plant construction
Food processing
Chemical engineering
Sterilizer construction, temperature control
Gas dosing
Conveyor systems for various bulk material (also sensitive
foodstuff)

english

Type 2301