beautypg.com

Burkert Type 2301 User Manual

Page 18

background image

18

Technical data

• Theoretical setting ratio (Kv

s

/ Kv

o

):

50 : 1 for seats DN 8 – DN 50
25 : 1 for seat DN 6
10 : 1 for seat DN 4

• Kv

R

value

9)

at 5 % of the lift for DN > 10 mm

Kv

R

value at 10 % of the lift for DN ≤ 10 mm

7.5.2 flow values

connection size
(flange)

actuator size

kv

s

values

Orifice dn (seat) [mm]

[mm]

[mm]

4

6

8

10

15

20

25

32

40

50

65

80

100

10

50

70

0.5

1.2

2.0

2.7

-

-

-

-

-

-

-

-

-

15

50

70

0.5

1.2

2.1

3.1

4.3

-

-

-

-

-

-

-

-

20

50

70

-

-

-

3.2

5.2

7.1

-

-

-

-

-

-

-

25

50

90

-

-

-

-

5.3

7.2

12.0

-

-

-

-

-

-

32

90

-

-

-

-

-

5.5

9.9

13.4

-

-

-

-

-

130

-

-

-

-

-

8.0

13.0

17.8

-

-

-

-

-

40

90

-

-

-

-

-

-

10.3

14.4

17.5

-

-

-

-

130

-

-

-

-

-

-

13.6

20.2

23.8

-

-

-

-

50

90

-

-

-

-

-

-

-

15.3

18.0

28.0

-

-

-

130

-

-

-

-

-

-

-

21.0

24.6

37.0

-

-

-

65

130

-

-

-

-

-

-

-

-

29.0

45.0

65.0

-

-

80

130

-

-

-

-

-

-

-

-

-

45.0

73.0

100

-

100

130

-

-

-

-

-

-

-

-

-

-

77.0

110

140

Tab. 7: Kv

s

values

9)

Kv

R

value = the smallest Kv value at which the angularity tolerance according to DIN / IEC 534-2-4 is still maintained.

english