Issue Number: 5

1

Read Me First Instructions

1.1

Data Sheet

You will need a copy of the data sheet your sales representative provided you for your

application. You will need to refer to the data sheet in order to set motor speeds and

dwell times.

1.2

Drive Size

You will need to determine which size drive you have for proper mounting and wiring.

1.3

Safety

Read Chapter 2 Safety Information before mounting or wiring the drive.
The STOP and START controls or electrical inputs of the drive must not be relied upon

to ensure the safety of the personnel. They do not isolate dangerous voltages from the

output of the drive or from any external unit. The supply must be disconnected by an

approved electrical isolation device before gaining access to electrical connections. The

drive contains capacitors that remain charged to a potentially lethal voltage after AC

supply has been disconnected. Wait at least 10 minutes for the stored charge to

dissipate. See section 2.9.4 Stored charge .

1.4

Mounting of Drive

The drive is designed to mount to a wall within a control panel or on a DIN rail. For

proper functioning, mount the drive with the minimum recommended clearances. See

Chapter 4.

1.5

Wiring Motor

The IMC high performance motor can be wired as either 200 or 400 volts. Wire the

motor as 200V for the A Size IM-pAC and wire the motor as 400V for the B Size IM-

pAC. See section 5.1, Figure 5-1 and Figure 5-2.

IMC Part Number

Drive

size

Motor Power

Rating

Drive

Color

92C85797010000

A

1 HP 0.75 kW 200 - 240V 0.75 kW single phase 48-62 hz IM-pAC

Blue

92C85797020000

B

1 HP 0.75 kW

380 - 460V 0.75 kW three phase 48-62 hz IM-pAC

Blue

92B90482010000 B 1.5 HP 1.1 kW 200 - 240V 1.1 kW single phase 48-62 hz SK Green
92B90482020000 B

2 HP 1.5 kW 200 - 240V 1.5 kW single phase 48-62 hz SK Green

92B90482030000 C

3 HP 2.2 kW 200 - 240V 2.2 kW single phase 48-62 hz SK Green

92B90482040000 B

2 HP 1.5 kW 380 - 460V 1.5 kW three phase 48-62 hz SK Green

92B90482050000 C 3 HP 2.2 kW 380 - 460V 2.2 kW three phase 48-62 hz SK Green
92B90482060000 C

5 HP 4.0 kW 380 - 460V 4.0 kW three phase 48-62 hz SK Green

92B90482070000 B

1 HP 0.75 kW 100-120V 0.75 kW single phase 48-62 hz SK Green

92B90482080000 B

1.5 HP 1.1 kW 100-120V 1.1 kW single phase 48-62 hz SK Green

92B90482090000 B

1.5 HP 1.1 kW 380 - 460V 1.1 kW three phase 48-62 hz SK Green

Single phase can be obtained from a 3 phase "wye" by wiring two of the "hots" (L1 and

L2 or L2 and L3 or L1 and L3) to the single phase control. Power supplied to the drive

must be from a balanced power supply with an earth ground. A floating ground or an

unbalanced supply can permanently damage the drive.