Defines the jog speed
Determines the input on terminal T2
0-20
: Current input 0 to 20mA (20mA full scale)
20-0
: Current input 20 to 0mA (0mA full scale)
4-20
: Current input 4 to 20mA with current loop loss (cL1) trip (20mA full scale)
20-4
: Current input 20 to 4mA with current loop loss (cL1) trip (4mA full scale)
4-.20
:Current input 4 to 20mA with no current loop loss (cL1) trip (20mA full scale)
20-.4
:Current input 20 to 4mA with no current loop loss (cL1) trip (4mA full scale)
VoLt
: 0 to 10V input
OFF
:Direction of rotation controlled by run forward and run reverse terminals
On
:Direction of rotation controlled by preset speed values (use run forward terminal)
Defines preset speeds 1 to 4.
Ld
: Active current as a % of motor rated active current
A
: Drive output current per phase in Amps
Fr
: Drive output frequency in Hz
SP
: Motor speed in rpm
Cd
: Machine speed in customer defined units (See Pr 24).
No
Function
Range
Defaults
Type
13
Not used
14
No
Function
Range
Defaults
Type
15
Jog reference
0 to 400.0 Hz
1.5
RW
No
Function
Range
Defaults
Type
16
Analog input 1 mode
0-20, 20-0, 4-20, 20-4,
4-.20, 20-.4, VoLt
6:VoLt
RW
In the 4-20 or 20-4mA modes (with current loop loss) the drive will trip on cL1 if the input
reference is below 3mA. Also, if the drive trips on cL1, the voltage analog input cannot
be selected.
NOTE
If both analog inputs (A1 and A2) are to be set-up as voltage inputs, and if the
potentiometers are supplied from the drive’s +10V rail (terminal T3), they must have a
resistance >4kΩ each.
NOTE
No
Function
Range
Defaults
Type
17
Enable negative preset speeds
OFF or On
OFF
RW
No
Function
Range
Defaults
Type
18
Preset speed 1
±1500 Hz
(Limited by setting of Pr 02
Maximum set speed
)
57
RW
19
Preset speed 2
0.0
20
Preset speed 3
0.0
21
Preset speed 4
0.0
No
Function
Range
Defaults
Type
22
Load display units
Ld, A
Ld
RW
No
Function
Range
Defaults
Type
23
Speed display units
Fr, SP, Cd
0:Fr
RW