b) You should have a copy of the data sheet for the indexer application in order to set
Pr 18 correctly. You must change Pr 10 (Security Level) to 2 or L3 before you can change
Pr 18, the preset speed. On the data sheet you will find the motor speed for your
application and the motor's rated rpm.
Use the following calculation to determine Pr 18.
Pr 18 = Pr 39 x Motor Speed for Application / Motor Rated RPM
Pr 18 = 60 hz x 1650 rpm / 1750 rpm = 57 hz (round all values up to a whole number)
NOTE
Parameter
Description
Value
Units
Pr 01
Minimum set speed
0
Hz
Pr 02
Maximum set speed
60
Hz
Pr 03
Acceleration rate 1
0.1
s/100Hz
Pr 04
Deceleration rate 1
0.2
s/100Hz
Pr 05
Drive configuration
3:Pr
Pr 06
Motor rated current
1.14
A (from motor plate)
Pr 07
Motor rated full load rpm
0
RPM (always 0)
Pr 08
Motor rated voltage
230
V (from motor plate)
Pr 09
Motor rated power factor
0.74
(from motor plate)
Pr 10
Security status
2:L3
Pr 11
Start / stop logic select
0
Pr 12
Brake controller enable
0:dis
Pr 15
Jog reference
1.5
Hz
Pr 16
Analog input 1 mode
(terminal T2)
6:VoLt
Pr 17
Allow negative
references
OFF
Pr 18
Preset speed 1
57
Hz (See note b)
Pr 19
Preset speed 2
0
Hz
Pr 20
Preset speed 3
0
Hz
Pr 21
Preset speed 4
0
Hz
Pr 22
Load display units
Ld
Pr 23
Speed display units
0:Fr
Pr 24
Customer defined scaling
1
Pr 25
User security code
0
Pr 27
Power-up keypad
reference
0
Pr 28
Parameter cloning
0:no
Pr 29
Load defaults
0:no
Pr 30
Ramp mode select
3:FSt.Hv
Pr 31
Stopping mode select
1
Pr 32
Dynamic V to f select
OFF
Pr 33
Catch a spinning motor
select
0
Pr 34
Terminal B7 mode select
0:dig
Pr 35
Digital output control
(terminal B3)
0:n=0
Pr 36
Analog output control
(terminal Bi)
0:Fr