DE-STA-CO IM-pAC AC Drive Getting Started Guide User Manual
Page 20
![background image](/manuals/322024/20/background.png)
20
IM-pAC Getting Started Guide
www.camcoindex.com | www.destaco.com
Issue Number: 5
1.22
Drive parameter list for using a PLC to control speed
10 Vdc applied to T1 and T2 will run the motor to the Pr 02 Maximum set speed. The
speed is proportional to the applied voltage.
NOTE
Parameter
Description
Value
Units
Pr 01
Minimum set speed
0
Hz
Pr 02
Maximum set speed
60
Hz
Pr 03
Acceleration rate 1
0.1
s/100Hz
Pr 04
Deceleration rate 1
0.2
s/100Hz
Pr 05
Drive configuration
2:AI.Pr
Pr 06
Motor rated current
-
A (from motor plate)
Pr 07
Motor rated full load rpm
0
RPM (always 0)
Pr 08
Motor rated voltage
-
V (from motor plate)
Pr 09
Motor rated power factor
-
(from motor plate)
Pr 10
Security status
0:L1
Pr 11
Start / stop logic select
0
Pr 12
Brake controller enable
0:dis
Pr 15
Jog reference
1.5
Hz
Pr 16
Analog input 1 mode
(terminal T2)
6:VoLt
Pr 17
Allow negative
references
OFF
Pr 18
Preset speed 1
0
Hz
Pr 19
Preset speed 2
0
Hz
Pr 20
Preset speed 3
0
Hz
Pr 21
Preset speed 4
0
Hz
Pr 22
Load display units
Ld
Pr 23
Speed display units
0:Fr
Pr 24
Customer defined scaling
1
Pr 25
User security code
0
Pr 27
Power-up keypad
reference
0
Pr 28
Parameter cloning
0:no
Pr 29
Load defaults
0:no
Pr 30
Ramp mode select
3:FSt.Hv
Pr 31
Stopping mode select
1
Pr 32
Dynamic V to f select
OFF
Pr 33
Catch a spinning motor
select
0
Pr 34
Terminal B7 mode select
0:dig
Pr 35
Digital output control
(terminal B3)
0:n=0
Pr 36
Analog output control
(terminal Bi)
0:Fr
Pr 37
Maximum switching
frequency
12
kHz
Pr 38
Auto-tune
0
Pr 39
Motor rated frequency
-
Hz (from motor plate)
Pr 40
Number of motor poles
2:4 pole