beautypg.com

DE-STA-CO IM-pAC AC Drive Getting Started Guide User Manual

Page 22

background image

22

IM-pAC Getting Started Guide

www.camcoindex.com | www.destaco.com

Issue Number: 5

1.24

How to configure the IM-pAC drive to trip for a current over-
load.

Overview
The IM-pAC drive is factory preset to constantly monitor the current seen by the motor

and the drive will trip if the accumulated motor current values over time exceed a set

value. This is a calculation and does not require a wired motor themistor input.
The motor thermal constant parameter controls the drive trip and is set at a default value

of 89. The 89 value will allow the motor to draw 1.65 times its rated amperage for a little

over 40 seconds before the drive will trip. When the drive trips the drive healthy relay

(T5 and T6 contacts) will open to signal the trip. You will wire your PLC input line

through the drive healthy relay to signal the trip. When the drive is tripped the display

will show [It.AC]
The overload configuration scheme for the IM-pAC uses a thermal constant parameter

set to 1 (the minimum) and a symmetrical current value set for the application. Index

drives 601RDM and 902RDM have been tested at IMC using a thermal constant of 1

and a symmetrical current constant of 165. The drives successfully tripped without any

indexer damage for a jammed dwell or an obstruction encountered during the middle of

the index.
For now based upon our test results we are limiting use of this overload
configuration to applications under 1 horsepower demand.
The following steps describe how to view the torque required for you application and

how to change the symmetrical current and motor constant values to protect your

indexer from damage.
We are assuming that you have already entered in the correct parameter values for

Pr 39, Pr 06, Pr 08 and Pr 09 from your motor name plate.
We also assume you have placed the jumpers and wired your motor for the correct

applied voltage. Remember the control voltage must be greater than or equal to the

motor's voltage.
The instructions in this document are detailed and should be read carefully before

proceeding. In addition we have included as a reference on the last page of this paper a

page from the IM-pAC manual showing how to view and change parameters from the

keypad.
Parameters Used
Parameter

Description

Pr 10

Security level - default is L1

Pr 88

Current magnitude - current demand for your application

Pr 4.07

Symmetrical current value - default is 165 percent

Pr 4.15

Motor thermal constant - default is 89

The key pad display should show [ih 0.0] and not [rd 0.0] when you start. You must put

the control into inhibit mode by opening B2 and B4.

The current overload configuration will protect the index drive only and is not meant to

be a means of protecting any personnel or tooling. Always make sure that no person is

near the indexer and the indexer is clear of any obstructions before operating the drive

while testing the configuration settings or during normal operation.

WARNING