Alpha Technologies AMP24 HP User Manual
Page 99
97
Doc. #: 0260011-J0 Rev B
;381;
;AC 1 : Vac_in Low Transfer;
;81.5; ;V;
x
ACin Voltage where a lower value transfers the load from the AC/AC converter to the DC/
AC converter
x
Range: 80 to 143, default: 81.5 V
;382;
;AC 1 : Vac_in Low Stop;
; 81.5; ;V;
x
ACin Voltage where a lower value causes the AC/AC converter to stop
x
It is possible to step down to 150 Vac. In this case, the AC/DC converter runs at a lower
power. The DC/DC converter supplies the rest (ONLY if DC is available, if not, there is a
derating)
;383;
;AC 1 : Vac_in High Start;
; 140; ;V;
x
ACin Voltage where a lower value causes the AC/AC converter to re-start
;384;
;AC 1 : Vac_in High Transfer;
;143; ;V;
x
ACin Voltage where a higher value transfers the load of the charge from the converter AC/
AC to the DC/AC converter
;385;
;AC 1 : Vac_in High Stop;
;143; ;V;
x
ACin Voltage where a higher value causes the AC/AC converter to stop
;390;
;AC 2 : Vac_in Low Start;
;91.5 ;V;
;391;
;AC 2 : Vac_in Low Transfer;
;81.5; ;V;
;392;
;AC 2 : Vac_in Low Stop;
;81.5; ;V;
;393;
;AC 2 : Vac_in High Start;
;140; ;V;
;394;
;AC 2 : Vac_in High Transfer;
;143; ;V;
;395;
;AC 2 : Vac_in High Stop;
;143; ;V;
x
The same for Group AC 1
;400;
;AC 3 : Vac_in Low Start;
;91.5 ;V;
;401;
;AC 3 : Vac_in Low Transfer;
;81.5; ;V;
;402;
;AC 3 : Vac_in Low Stop;
;81.5; ;V;
;403;
;AC 3 : Vac_in High Start;
;140; ;V;
;404;
;AC 3 : Vac_in High Transfer;
;143; ;V;
;405;
;AC 3 : Vac_in High Stop;
;143; ;V;
x
The same for Group AC 1