3 inverter module indicators, Figure 48 — inverter module status, power leds, Figure 49 — output power indicator leds – Alpha Technologies AMP24 HP User Manual
Page 65: 1 status leds

63
Doc. #: 0260011-J0 Rev B
6.3 Inverter Module Indicators
6.3.1 Status LEDs
Inverter Status LED
Description
Remedial action
OFF
No power or forced stop
Check AC input
Permanent green
Input OK, normal operation
None required
Flashing green
Inverter OK but conditions are not
within normal parameters
Check upstream and surrounding
equipment
Flashing green/orange alternating Recovery mode after boost
(10 In short circuit condition)
Wait for a while
Permanent orange
Starting-up mode
Wait
Flashing orange
Modules cannot start
Insert CXCU
Flashing red
Recoverable fault
Wait or attempt to clear fault condition by
removing and reinserting the module
Permanent red
Non recoverable fault
• Attempt to clear fault condition by
removing and reinserting the module
• Download CXCU inverter alarm logs
• Record the alarm(s)
• Send module back for repair
Output Power (redundancy not counted)
The output power LEDs (located on the right side of the module’s front panel indicate the amount of
power (percentage of rated power) provided by the module. The number of bars that are illuminated
combined with whether or not they are on steady or flashing indicate the output power level or
overload condition as shown in Figure 49.
Output power
indicator LEDs
Status LEDs
Figure 48 — Inverter module status, power LEDs
AC input
AC output
DC input
< 5%
Flashing
5% to 40%
On steady
40% to 70%
On steady
80% to 95%
On steady
100%
On steady
100% Overload
Flashing
Figure 49 — Output power indicator LEDs
Load: