10.4 Inverter Parameters (ID 51 – 550)
;60;
;Input Source (AC : 0, DC : 100);
;0; ;%;
x
Record of priority source
x
0 –> Priority feed from ACin (converter AC/AC - AC/AC mode), Default setting
x
100 –> Priority feed from DC (converter DC/AC - On Line mode)
;61;
;AC
in
Mode (0 : normal, 1 : Safe);
;0; ; ;
x
Opens the AC
in
inlet relay
x
0 –> Normal running in AC/AC mode, Default setting
x
1 –> ACin inlet relay is open and so the system is insulated from the Mains
;62;
;Walk-in Mode (0 : No, 1 : Yes) ;
;1; ; ;
x
Walk-in mode allows a progressive comeback, slowly removing DC power while slowly
increasing AC power
x
0 –> no progressive switching
x
1 –> progressive switching at 10% per second
;70;
;Number of phases ;
;3; ; ;
x
Record of number of phases : 1 (Single phase), 2 (2 phase), 3 (3 phase)
x
Range: 0 - 8, Default: 1
;71;
;Mode (0 star; 1 Delta) ;
;1; ; ;
x
Record of the protection for working on Delta load
x
The mode, star or delta, allows configuration of automatic protection when the load is a
delta connection (an engine for instance). This protects the load when 1 phase is lost. The
protection consists of switching off all inverters.
x
0 –> no delta load protection, Default setting
x
1 –> Delta load protection available
;75;
;Free running Frequency ;
;50.0; ;Hz;
x
Record of the Inverters system frequency, 50 or 60 (default)