9.3 System Specifications
System AC Input (P/N 0140004)
Nominal Voltage (AC)
120 V
Input Power Factor
>99%
Frequency
60 Hz
Synchronization Range
57-63 Hz
System DC Input
Nominal Voltage
48 Vdc
Voltage Range (max)
40-60 Vdc (user adjustable)
Max DC input current @ 48 Vdc
389 A
Max DC input current @ 40 Vdc
467 A
Unified System Controller with SNMP
Control & Monitoring
Configure, control and monitor Inverter & Rectifier modules
via Internet Explorer 7 and onwards
Display
LCD Touchscreen display
OK / Major / Minor 3-color LED display
Web-based GUI via Ethernet
Communication Ports
RJ45 Ethernet Port
Controller I/O
Voltage Inputs
0
Temperature Inputs
2
Current Inputs
1
Bivoltage Inputs
0
Digital Inputs
2
Relay Outputs
6
Environmental Specifications
Operating Temperature (full load)
-20° to 50°C (-4° to 122°F)
Storage Temperature
-40° to 70°C (-40° to 158°F)
Relative Humidity
Up to 95%, non-condensing
Operating Altitude
Up to 1,500 m (4,900 ft) above sea level
Heat Dissipation Per Module
286 BTU/hr in AC-to-AC mode
410 BTU/hr in DC-to-AC mode
Mechanical Specifications
No of shelves
System Dimensions H x W* x D
mm (in)
System Weight -- without modules
kg (lb)
4
622 x 443 x 432 (24.5 x 17.44 x 17)
52 (115)
3
533 x 443 x 432 (21 x 17.44 x 17)
45 (100)
2
444.5 x 443 x 432 (21 x 17.44 x 17)
39 (85)
1
355.6 x 443 x 432 (21 x 17.44 x 17)
32 (70)
*Width with mounting ears
19" rack mount option: 492.8mm/ 19.4"
23" rack mount option: 584.2mm/ 23"
Agency Compliance
CSA
C22.2 107.3-05
UL
UL1778; Issue 4
(shelves and modules)
EMC
FCC CFR47 Part 15 Class A; ICES-003