Alpha Technologies AMP24 HP User Manual
Page 96

Doc. #: 0260011-J0 Rev B
94
;101;
;Remote OFF disable ACin Power;
;0; ; ;
x
0 –> Normal mode, default
x
1 –> ACin power is de-activated
;102;
;Negative Power (0 : OFF, 1 : ON);
;1; ; ;
x
1 –> ON, default
;103;
;External clock (0 : OFF, 1 : ON);
;0; ; ;
x
0 no in service protection
x
1 in service protection
;160;
;OUT 1 : phase shift (-180 to 360, default 0);
;0; ;deg;
;161;
;OUT 1 : Nominal Output Voltage (100 to 140);
;120; ;V;
x
Record of the phase shift and nominal Outlet voltage.
x
Phase shift range: -180 to 360, default: 0 deg
x
Nominal output voltage range: 100 to 140, default: 120 V
;170;
;OUT 2 : phase shift;
;120; ;deg;
;171;
;OUT 2 : Nominal Output Voltage;
;120; ;V;
x
Record the phase shift and the nominal Outlet voltage.
x
Range and defaults same as OUT 1
;180;
;OUT 3 : phase shift;
;240; ;deg;
;181;
;OUT 3 : Nominal Output Voltage;
;120; ;V;
x
Record the phase shift and the nominal Outlet voltage.
x
Range and defaults same as OUT 1
Parameters for DC Groups
;260;
;DC 1 : Vdc_in Low Start;
;49; ;V;
x
Low DC Voltage – a higher value causes the converter DC/AC to re-start
x
Range: 39 to 61, default: 49 V