60

6.2.6  Manage Config File

The inverter settings have their own configuration and are not part of the full site configuration file.

Refer to Chapter 10 for a list of the configuration file parameters and steps to save the file and upload

it to another system.

6.2.7  Alarms

Standard Inverter Alarms

Alarms for the following conditions can be configured from the

Alarms > Configure Alarms

menu

category (refer to the controller software manual for more details on alarm configuration):

Alarm Name

Alarm Condition

Inverter Major Fail Count

Number of failed Inverters equals or exceeds a user configured threshold

Inverter Minor Fail Count

Number of failed Inverters equals or exceeds a user configurable

threshold

Inverter Comms Lost

Controller loses communications with any one inverter. The number of

inverters must be correctly identified in the Inverters > Set Output menu.

Inverter AC Input Fail

Main AC input of the inverter is lost

Inverter Alarm

Any individual or system alarm is detected

Figure 43 — Configure alarms window

Custom Inverter Alarms—Mapping Alarms to Relays

Custom inverter alarms can be mapped through the digital inputs to available relays. Refer to the

latest version of the CXCU Controller software manual.