Table K — Inverter Alarm Codes

Alarm Type

Description

Cause

Solution

13 Vout INVERSE

Error in the self-test during

the starting process

This error happens if the

module is not configured on

the correct output phase

Verify the phase configuration

of the modules. Then, reset

the module and try again. If

the problems still happens,

replace the module

14 OVRLOAD TOO

LONG

Output voltage too low due

overload for a long time

Load too higher for the

inverter quantity operational

on system.

Reduce load or add inverter

on the system.

15 OUT FUSE

FAILURE

Module is delivering no

power to the load while the

other module on the same

phase does.

Output fuse open / problem

in the connection of ACout

Check if the problem can be

caused by something external

to the module. If not, replace

the module

16 VoutIout TOO

LOW

Output voltage is too low

while the output current is in

an acceptable range

Problem inside the module.

Reset the module and try

again. If the problems still

happens, replace the module

18 VoutPout TOO

LOW

Output voltage is too low

while the output power is in

an acceptable range

Problem inside the module.

Reset the module and try

again. If the problems still

happens, replace the module

19 RAM FAILURE

Values in the RAM are

corrupt

Replace the module

Error recoverable

33

OUT OF SYNC Inverter is not synchronised

on other inverters

Problem on the

communication bus

Check bus.

Problem inside the module

Replace the module

34

TEMP TOO

HIGH

Temperature on heat sink

too high

Temperature too high in the

room, cooling insufficient, or

inverter component defective

Check temperature inside

inverter. Check room

temperature. Replace FAN.

Replace inverter

35

COM BUS

FAILURE

The inverter doesn't see

itself on the bus

Problem on bus or internal

problem

Check bus / replace module

36

COM BUS

CONFLICT

2 TSI have same ADX

Will self repair

37

NO POWER

SOURCE

No input AC and DC

available on inverter

No supply voltage

Check AC input voltage at AC

input and DC input terminals

Circuit Breaker open

Check Circuit breakers

Wiring fault

Check input voltage at

38

COM BUS

FAILURE

TSI must have a T2S to

start

No T2S in the system

Add a T2S

39

PARAM QUERY Inverter is updating his

parameters

Part of starting process

Nothing to do

40

PARAM

MISMATCH

Configuration file

incompatible with TSI

inverter

Problem with parameters

Check configuration file and

re-send it

41

PHASE NOT

READY

The phase inverter is not

configured for this phase (

multiple phase system)

AC not present, or phase not

configured

Reconnect AC IN, configure

the inverter phase

42

STATUS 42

43

INV MISMATCH Inverter incompatible with

inverter installed in system

Inverter for pack solution.

Limitation to 6 inverter on the

same BUS

Remove incompatible inverter