Doc. #: 0260011-J0 Rev B
;80;
;Short Circuit Voltage Threshold;
;80; ;V;
x
Minimum Voltage Threshold where module considers that outlet is in short circuit
x
Adjustable from 20 to 100 Vac, default: 80 Vac
;81;
;Short Circuit Hold Time;
;60.0; ; sec;
x
Time Duration when the module tries to eliminate the short-circuit existing on the outlet
x
When this time expires and the voltage is less than the value on line 80, the module stops.
x
Adjustable from 0.1 to 600 sec, default: 60 sec
;82;
;Booster 10 x I
in
(0 : OFF, 1 : ON) ;
;1; ; ;
x
Turns off the Booster option which generates a current of 10 x I
in
for 20ms in case of short-
circuit.
;90;
;Max current (as percentage of nominal current);
;110; ;%;
x
Maximum Current that module can supply.
x
Adjustable from 100 to 110 % for AIM2500
;91;
;Max power (as percentage of of nominal power) ;
;110; ;%;
x
Maximum Power that the module can supply.
x
ALWAYS RECORD THE SAME VALUES for 90 and 91
;92;
;Max Overload Duration);
;15; ;sec;
x
Maximum Time Duration when module can run with overload.
x
Adjustable from 0 to 15 sec, default: 15 sec
;100;
;Synchronization Tracking Speed;
;0; ; ;
x
Speed with which the module tries to synchronize AC
out
x
Possible values:
Speed
Value
Frequency (Hz/sec)
very fast
-2
2.5
fast
-1
1.25
normal (default)
0
0.5
slow
1
0.25
very slow
2
0.1