Alpha Technologies AMP24 HP User Manual
Page 98
Doc. #: 0260011-J0 Rev B
96
;290;
;DC 4 : Vdc_in Low Start;
;49; ;V;
;291;
;DC 4 : Vdc_in Low Transfer;
;42; ;V;
;292;
;DC 4 : Vdc_in Low Stop;
;42; ;V;
;293;
;DC 4 : Vdc_in High Start;
;58; ;V;
;294;
;DC 4 : Vdc_in High Transfer;
;61; ;V;
;295;
;DC 4 : Vdc_in High Stop;
;61; ;V;
x
The same as Group DC 1
;300;
;DC 5 : Vdc_in Low Start;
;49; ;V;
;301;
;DC 5 : Vdc_in Low Transfer;
;42; ;V;
;302;
;DC 5 : Vdc_in Low Stop;
;42; ;V;
;303;
;DC 5 : Vdc_in High Start;
;58; ;V;
;304;
;DC 5 : Vdc_in High Transfer;
;61; ;V;
;305;
;DC 5 : Vdc_in High Stop;
;61; ;V;
x
The same as Group DC 1
Synchronization with ACin source
;370;
;AC : Fac_in Low Start;
; 57.3; ;Hz;
x
Below this value and above parameter 371, the inverters will try to synchronize with the
ACin frequency
;371;
;AC : Fac_in Low Stop;
;57.0; ;Hz;
x
Below this value the inverters will stop trying to synchronize with the ACin frequency
;372;
;AC : Fac_in High Start;
;62.7; ;Hz;
x
Above this value and less than parameter 375, the inverters will try to synchronize with the
ACin frequency
;375;
;AC : Fac_in High Stop;
;63; ;Hz;
x
Above this value, the inverters will trying stop to synchronize with ACin
Parameters for AC Groups
;380;
;AC 1 : Vac_in Low Start;
;91.5; ;V;
x
ACin Voltage where a higher value causes the converter AC/AC to start
x
Range: 83 to 143, default: 91.5 V