Figure 38 — set output window, 1 set output – Alpha Technologies AMP24 HP User Manual
Page 59
57
Doc. #: 0260011-J0 Rev B
6.2.1 Set Output
Number of
modules:
The value is the number to be acquired by the CXCU. An invalid setting will result in an
alarm condition:
Inverter Comms Lost
; i.e., the number of modules must agree with the
actual number of inverters mapped to that particular group.
Amount of
Redundancy:
Number of inverters considered redundant
Phase shift:
Assign a phase shift (in degrees) to the AC output group
1
2
3
Single phase
0
N/A
N/A
Split phase (120/240 V)
0
180
N/A
2-pole (120/208 V)
0
120
N/A
3-phase (120/208 V)
0
120
240
If the actual phase rotation of the AC Input is not 1 – 2 – 3 (i.e. it may be 1 – 3 – 2),
alarms will result. See NOTE below.
Nominal Output
Voltage
Sets the target output AC voltage and must be used with caution; the devices
connected to the inverters could sustain damage due to irregular AC voltage.
Verify that the Phase Shift is set correctly before
mapping inverters in the new groups and turning
them on.
Figure 38 — Set Output window
Alarm code (41) PHASE NOT READY and/or (175) AC OUT NOT SYNCHRONIZED indicate that the phase
rotation of the AC Input is not correct. (The inverters will not start until the phase and rotation are correct.)
To remove the alarm, return to
Inverters -> Set Output
and correct the phases as shown:
1
2
3
2-pole (120/208 V) °
0
240
N/A
3-phase (120/208 V) °
0
240
120
NOTE:
CAUTION!
The value entered in the Nominal Output Voltage field can change the actual AC output
voltage of the inverters. Setting this value to anything other than 120 V will render the UL/
CSA approval invalid.