10.5 Alarm Settings (ID 551-950)
Global Parameters (ID: 551-600)
;551;
;Alarm on prog. relay (255 is NU);
;255; ; ;
x
Replace 255 by the Alarm Code you wish for programming the relay user selectable 3
x
See previous codes for the T2S and Enclosed list for the TSI.
;553;;
;MAJ relay temporization;
;60; ;sec;
x
Temporization of Urgent alarm (from 0 to 65536 sec)
;554;
;MIN relay temporization;
;30; ;sec;
x
High DC voltage – a higher value re-starts the DC/AC converter
;556;
;Saturation alarm threshold;
;100; ;%;
x
Level of load that generates an alarm indicating there is a risk of overload.
x
This parameter takes into account the redundancy defined previously
x
I.e. P ex : system with 4 modules with 1 redundant –> 80 % of 3 modules
;558;
;AC
in
is present (1:true 0:false);
;1; ; ;
x
Allow to inhibit the alarm when ACin not Present
x
1 –> gives alarm when main Network is not Present
x
0 –> no alarm when main Network is not Present (AC in not available or Regular inverter)
;570;
;Log near. full thresh. (100-200);
;180; ; ;
x
Number of messages in the Logfile. It is from the Logfile that alarm is generated when the
Logfile is about completed.
Configuration of types of Alarms
- Alarm Type (ID : 601 - 900) : Minor(1) - Major(2) - No Alarm(0)
x
Choice for type of alarms as detailed hereafter
x
No Alarm = 0 / Minor = 1 / Major = 2
;828;
;227.DIG INP1 FAILURE;
;0; ; ;
x
Type of alarms for Digital inlet 1 (Inlet to be configured by user)