7. Preventive Maintenance
This equipment requires regular maintenance. Maintenance must be performed by qualified service
personnel only. Contact Alpha Technologies at 1-888-462-7487 for any assistance with maintenance.
WARNING!
WARNING: HIGH VOLTAGE AND SHOCK HAZARD Use extreme care when working in-
side the enclosure/shelf while the system is energized. Do not make contact with live com-
ponents or parts. Static electricity may damage circuit boards, including RAM chips. Always
wear a grounded wrist strap when handling or installing circuit boards. Ensure redundant
modules or batteries are used to eliminate the threat of service interruptions while perform-
ing maintenance on the system’s alarms and control settings.
7.1 Recommended maintenance schedule
Task:
Interval
Clean ventilation openings
1-6 month
Inspect all cable connections, re-torque if necessary
1 year
Verify alarm/control settings
1 year
Verify alarm relay operation
1 year
Verify circuit breaker operation
1 year
Battery maintenance
3 months
7.2 Tools and Equipment
Table I — Tools
Required
Service /Maintenance
Commissioning
Torque wrench
X
X
#2 Philips screw driver
X
X
#2 flat head screw driver (3/16") width head
X
#1 flat head screw driver (1/8") width head
X
Small flat head screw driver (1/16") width head
X
X
9/16" hex driver
X
3/8" hex driver
X
7/16" combo wrench
X
7/16" flat gear ratchet
X
9/16" combo wrench
X
9/16" flat gear ratchet
X
11/16" combo wrench
X
11/16" flat gear ratchet
X
6" ratchet extension
X
3" ratchet extension
X
3/8" ratchet socket
X