Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Operators Guide Rev. D User Manual
Page 77
TroubleShooting & Maintenance
Page
5 - 3
5
TABLE 5 - 1 (C
ONTINUED
... )
ALARMS & ERROR MESSAGES
Keep accurate and dated records, or printouts, of all alarms — when they happen and
when they clear.
Contact your Tank Sentinel service provider if the same alarms occur
often or repeatedly... multiple alarms are not normal.
NOTE
☞
NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
23
AUXILIARY INPUT
SENSOR
Auxiliary input detected on channel 1 or 2
(follow
policy procedure at your site).
24
CPM LOW CURRENT
SENSOR
Current of Rectifier dropped below the threashold
value (a Tank Sentinel setting) (follow
policy procedure at your site)
25
DRY WELL
SENSOR
TSP-MWS ground water Monitoring Well
BriteSensor is not submerged in water @ Channel
#N
(it cannot detect a product leak unless it's
submerged in ground water... the well may not be
deep enough or the sensor long enough... contact
service provider)
26
EXTERNAL INPUT
SENSOR
External N input module has detected an input
signal
(follow policy procedure at your site).
27
HIGH BRINE
SENSOR
TSP-HIS BriteSensor @ Channel #N detected a
High Brine level
(Call service provider [to confirm
leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)
28
LIQUID DETECTED / LIQUID
SENSOR
Standard Sensor @ Channel #N detected a liquid
(run a tank leak test [depending on the sensor
location] and call service provider to identify the
liquid and retest sensor)
29
LOW BRINE
SENSOR
TSP-HIS BriteSensor @ Channel #N detected a
Low Brine level
(Call service provider [to confirm
leak] and call your local Regulatory agency. Shut
down pump & dispenser if a leak test has failed on
that tank and see procedures at your site.)
30
PRODUCT PRESENT /
PRODUCT DETECTED
SENSOR
TSP-DIS, -DDS, -DTS, -MWS BriteSensor @
Channel #N detected Product / leak
(Call service
provider [confirm leak] call the local Regulatory
agency. Shut down pump & dispenser for that
tank and see procedures at your site. [replace
sensor])
31
STANDARD ALARM /
STANDARD INPUT
SENSOR
A Standard Sensor (type TSP-EIS, -HLS, -ULS) @
Channel #N has detected liquid
(run a tank leak
test [depending on the sensor location] and call
service provider to identify the liquid and retest
sensor)