Space, Generator run report – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Operators Guide Rev. D User Manual
Page 65
3
Page
3 - 30
Tank Sentinel Operator’s Guide
Sample Reports (C
ONTINUED
... )
Generator Run REPORT
This report shows when the generator started (
BEGIN
)
and stopped (
END
) and the fuel consumed (
USAGE &
USAGE RATE
) during the run.
This report is available only with consoles that have the
special Emergency Generator application software.
Press:
Press:
Report Choices
+
2 x
Print Test REPORT
This report (at left without the standard header) checks
the operation and function of the printer. The printing
should be uniformly dark, clear, and legible.
Press:
and
Generator Run Report:
Gen Run
M1
Choose Printer
or Fax
Press the DOWN key to show this report.
Displayed with Emergency Generator
Applications only.
M1
J
W
REPORT
9
K
X
DOWN
SPACE
M
Z
CHECK
.
M2
RIGHT
INCON
INTELLIGENT CONTROLS INC.
P.O. BOX 638
SACO ME 04072
1-800-984-6266
6/17/2002
2:15 PM
GENERATOR RUN REPORT
INPUT
AUXILIARY 1
TANK 1
3918.47
GAL
PROD 1 #2 FULE OIL
BEGIN TIME
10:45 AM
BEGIN DATE
06/17/2002
BEGIN GROSS
3136.2 GAL
BEGIN NET
3129.4 GAL
BEGIN LEVEL
26.775 IN
BEGIN WATER
1.120 IN
BEGIN WATER
24.5 GAL
BEGIN TEMP
68.459 F
END TIME
11:58 AM
END DATE
06/17/2002
END GROSS
3118.3 GAL
END NET
3118.5 GAL
END LEVEL
24.875 IN
END WATER
1.120 IN
END WATER
24.5 GAL
END TEMP
68.559 F
GROSS USAGE
17.9 GAL
NET USAGE
15.0 GAL
USAGE RATE
13.250 GPH