beautypg.com

Space, Generator run report – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Operators Guide Rev. D User Manual

Page 65

background image

3

Page

3 - 30

Tank Sentinel Operator’s Guide

Sample Reports (C

ONTINUED

... )

Generator Run REPORT

This report shows when the generator started (

BEGIN

)

and stopped (

END

) and the fuel consumed (

USAGE &

USAGE RATE

) during the run.

This report is available only with consoles that have the
special Emergency Generator application software.

Press:

Press:

Report Choices

+

2 x

Print Test REPORT

This report (at left without the standard header) checks
the operation and function of the printer. The printing
should be uniformly dark, clear, and legible.

Press:

and

Generator Run Report:

Gen Run

M1

Choose Printer

or Fax

Press the DOWN key to show this report.

Displayed with Emergency Generator

Applications only.

M1

J

W

REPORT

9

K

X

DOWN

SPACE

M

Z

CHECK

.

M2

RIGHT

INCON

INTELLIGENT CONTROLS INC.

P.O. BOX 638

SACO ME 04072

1-800-984-6266

6/17/2002

2:15 PM

GENERATOR RUN REPORT

INPUT

AUXILIARY 1

TANK 1

3918.47

GAL

PROD 1 #2 FULE OIL

BEGIN TIME

10:45 AM

BEGIN DATE

06/17/2002

BEGIN GROSS

3136.2 GAL

BEGIN NET

3129.4 GAL

BEGIN LEVEL

26.775 IN

BEGIN WATER

1.120 IN

BEGIN WATER

24.5 GAL

BEGIN TEMP

68.459 F

END TIME

11:58 AM

END DATE

06/17/2002

END GROSS

3118.3 GAL

END NET

3118.5 GAL

END LEVEL

24.875 IN

END WATER

1.120 IN

END WATER

24.5 GAL

END TEMP

68.559 F

GROSS USAGE

17.9 GAL

NET USAGE

15.0 GAL

USAGE RATE

13.250 GPH