5 troubleshooting & routine maintenance 5, Troubleshooting 5, Table 5 - 1 alarms & error messages 5 – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Operators Guide Rev. D User Manual
Page 75: 5troubleshooting, Routine maintenance, Troubleshooting
TroubleShooting & Maintenance
Page
5 - 1
5
5
TroubleShooting
&
Routine Maintenance
TroubleShooting
Contents: Silencing Alarms
(see
ACK
key – Chapter 1, and
Acknowledging Alarms Chapter 2)
Alarms & Error Messages (TABLE 5 - 1)
System Test Schedule (TABLE 5 - 2)
Important Policy & Procedures at Your Site
(Silencing Alarms, Acknowledging Alarms,
Grace Period Allowed (# of times)
TABLE 5 - 1
ALARMS & ERROR MESSAGES
Troubleshooting Alarms & Error messages,
Line and Tank Leak Test Failures
Call Numbers & FAX No’s (TABLE 5 - 3) )
DO Before & After Installation / Upgrade
Site Sketch
Routine Maintenance (External Cleaning,
Replacing Printer Paper Roll, Fuses, &
Battery & Internal Cleaning)
NOTE: Diagnostic text in the left column, is shown bolded { become alarms if active for 48 hours }
#
Printed / Faxed / Displayed
Alarm / Warning Text:
Alarm Type:
System WARNING / Error Descriptions and
ALARM Descriptions
(actions to take)
1
0.1 GPH LINE LEAK
DETECTED
LINE
For LINE # N: Line Leak Detected / Leak Test
Failed
(1. Inspect dispense area for leaks 2.
Retest if no leaks seen 3. Shut off pump /
dispenser power
2
0.1 GPH ABORT (DISPENSE)
LINE
Attempted dispense causes the annual line leak
test to aborted (dispensing is not allowed during
this test). To allow dispensing: push the RESET
/ TEST button on the TS-LLD Control Unit that is
flashing the 80 alarm-error-code.
See the TS-LLD
Quick Reference Guide about the 0.1 gph Annual
Test and requirements.
0.1 GPH LINE LEAK
(Continued… )
LINE
4. Second failure: Call Service provider / local
Regulatory Agency / Manager per policy
procedure at your site).
3
0.1 GPH LINE TEST
ABORTED
LINE
The annual precision line leak test was
intentionally canceled / aborted from the Tank
Guage or from the TS-LLD control unit.
4
0.2 GPH LINE LEAK
LINE
Follow the steps detailed above for 0.1 gph Line
Leak Detected
5
3 GPH LINE LEAK
LINE
LINE # N - Line Leak Detected / test failed Large /
gross leak
(see above 0.2 gph line leak & follow
steps 3, 1, and 4 in this order).
6
BLK TUB/LSU BLOCKED
TUBE
LINE
(Push RESET / TEST button on the TS-LLD
control unit that is flashing an 81 Alarm-error code
and call for cleaning service).
7
CU COMM/CU COMM
FAILURE
LINE
Communications was lost between the Tank
Sentinel console and TS-LLD Control Unit
…(call
for service).
8
LINE OUT OF COMPLIANCE
LINE
33 or more days have passed since a 0.2 gph line
leak tes has finished and passed
(prevent
dispense attempts until the monthly test passes)