Error detection and elimination – Elmo Rietschle 2FC4...-1CB User Manual
Page 63

Error detection and elimination
8
© Gardner Denver Deutschland GmbH
63
/
74
05.2014 · 610.00260.40.000
No. Error name
Error description
Possible cause / remedy
13
External error 1
The parametrised error input is
active. 5.010
Eliminate external error
14
External error 2
The parametrised error input is
active. 5.011
Eliminate external error
15
Motor recognition
Motor identification errors
Check the connections to the
drive controller / motor and PC /
MMI hand-held unit / the drive
controller! Restart of the motor
identification!
16
IGBT trip
Protection of the IGBT module
from overcurrent has been trig-
gered
Short circuit in motor or motor
cable / controller settings
17
Intermediate circuit over-voltage The maximum intermediate
circuit voltage has been ex-
ceeded
Recovery through motor in re-
generative operation / mains
voltage too high / incorrect set-
ting of the speed controller /
braking resistor is not con-
nected or defective / ramp times
too short
18
Intermediate circuit undervolt-
age
The minimum intermediate cir-
cuit voltage was not reached
Mains voltage too low / mains
defective / check wiring
19
Motor overtemperature
Motor PTC has been triggered
Overload of the motor (e.g. high
torque at low speed) / ambient
temperature too high
20
Interruption in mains supply
One phase missing / mains volt-
age supply is interrupted
21
IGBT module overtemperature
IGBT module overtemperature
Insufficient cooling, low speed
and high torque, clock fre-
quency too high
22
Overcurrent
Maximum output current of the
inverter exceeded
Cooling insufficient / low speed
and high torque / clock fre-
quency too high / ramp times
too small / brake not opened
23
Drive controller overtemperature Internal temperature too high
Cooling insufficient / low speed
and high torque / clock fre-
quency too high / continuous
overload / reduce ambient tem-
perature / check fan
24 I
2
T motor protection switch-off
The internal I
2
T motor protection
(parametrisable) has been trig-
gered
Continuous overload
25
Grounding
Grounding of a motor phase
Insulation fault
26
Motor connection interrupted
No motor current despite con-
trol by the drive controller
No motor connected
27 Motor
parameter Plausibility
check of the motor
parameters has failed
Parameter set not OK
28 Drive
controller
parameters
Plausibility check of the drive
controller parameters has failed
Parameter set not OK, motor
type 33,001 and control mode
34,010 not plausible
29
Type plate data
No motor data has been en-
tered.
Enter motor data according to
the rating plate
30
Limitation of power classes
Max. overload of the drive con-
troller exceeded for more than
60 seconds.
Check application / reduce load
/ scale-up the drive controller
size