Parameters – Elmo Rietschle 2FC4...-1CB User Manual
Page 51

Parameters
7
© Gardner Denver Deutschland GmbH
51
/
74
05.2014 · 610.00260.40.000
Digital outputs
For the digital outputs 1 and 2 (DOx - illustration DO1/DO2)
4.150/4.170
DOx function
Unit: Integer
Relationship to
parameter:
4.151/4.171
4.152/4.172
Parameter HB:
S. xy
Transfer
status:
2
min: 0
Intrinsic value
(to be en-
tered!)
max: 50
Def:
4.150: 18
4.170: 19
Selection of the process variable to which the output should
switch.
0 = not assigned / integrated soft - PLC
1 = intermediate circuit voltage
2 = mains voltage
3 = motor voltage
4 = motor current
5 = actual frequency value
6 = -
7 = -
8 = IGBT temperature
9 = inner temperature
10 = error (NO)
11 = error inverted (NC)
12 = output stage release
13 = digital input 1
14 = digital input 2
15 = digital input 3
16 = digital input 4
17 = ready for operation
18 = ready
19 = operation
20 = ready for operation + ready
21 = ready for operation + ready + operation
22 = ready + operation
23 = motor power
24 = torque
25 = field bus
26 = analogue input 1 (above V3.60)
27 = analogue input 2 (above V3.60)
28 = PID setpoint (above V3.60)
29 = PID feedback (above V3.60)
50 = motor current limit active
4.151/4.171
DOx On
Unit:
Relationship to
parameter:
4.150/4.170
Parameter HB:
S. xy
Transfer
status:
2
min: -10000
Intrinsic value
(to be en-
tered!)
max: 10000
Def: 0
If the set process variable exceeds the switch-on limit, the out-
put is set to 1.
4.152/4.172
DOx Off
Unit:
Relationship to
parameter:
4.150/4.170
Parameter HB:
S. xy
Transfer
status:
2
min: -10000
Intrinsic value
(to be en-
tered!)
max: 10000
Def: 0
If the set process variable falls below the switch-on limit, the
output is set to 0.
7.3.8