Terminal no. Designation
(Terminal) assignment
15
A. Out 0 ... 10 V
Actual frequency value (parameter
4,100)
16
A GND (Ground 10 V)
Ground
17
A. In 1
External Setpoint source (parameter
1,130)
18
A GND (Ground 10 V)
Ground
19
A. In 2
Actual PID value (parameter 3,060)
20
A GND (Ground 10 V)
Ground
Terminal assignment X6 (relay 1)
Terminal no. Designation
(Terminal) assignment
1
COM
Centre contact relay 1
2
NO
Normally open contact relay 1
3
NC
Normally closed contact relay 1
In the factory setting, relay 1 is programmed as "fault relay" (parameter
4,190).
Terminal assignment X7 (relay 2)
Terminal no. Designation
(Terminal) assignment
1
COM
Centre contact relay 2
2
NO
Normally open contact relay 2
3
NC
Normally closed contact relay 2
In the factory setting, relay 2 is programmed as "fault relay" (parameter
4,210).
Wiring diagram
Control terminals
The drive controller is ready for operation after connection to a 400 V AC power
supply (to the terminals L1 to L3) or after connection to a 565 V DC power supply
(to the terminals L1 and L3).
Alternately, there is the option to put the drive controller in operation by connect-
ing an external 24 V voltage.
The required presetting is described in the chapter "System parameters".