Parameters – Elmo Rietschle 2FC4...-1CB User Manual
Page 60

7
Parameters
610.00260.40.000 · 05.2014
60
/
74
© Gardner Denver Deutschland GmbH
34.226
Starting current
Unit: %
Relationship to
parameter:
34.227
Parameter HB:
S. xy
Transfer
status:
2
min: 5
Intrinsic value
(to be en-
tered!)
max: 1000
Def: 25
Only for synchronous motors.
The flow which is set in the motor prior to its start can be ad-
justed here. Value in % of the rated motor current.
34.227
Initialisation time
Unit: s
Relationship to
parameter:
34.226
Parameter HB:
S. xy
Transfer
status:
2
min: 0
Intrinsic value
(to be en-
tered!)
max: 100
Def: 0,25
Only for synchronous motors.
The time in which the starting current is 34,226 is applied can be
set here.
34.228–
34.230
Start-up behaviour
Unit: Integer
Relationship to
parameter:
Parameter HB:
S. xy
Transfer
status:
2
min: 0
Intrinsic value
(to be en-
tered!)
max: 1
Def: 0
Only for synchronous motors.
Larger starting torques can be achieved by changing the start-
up procedure to the "controlled" mode.
0 = regulated, the inverter switches directly to the control mode
after the setting phase.
1 = controlled, following the setting phase, the field of rotation is
increased to the starting frequency 34,230 controlled with the
start-up ramp 34,229, then it is switched to the regulation mode.