Appendix I - Modbus Communications Points

Function

Modbus

Code

Point #

Point Description

Range/Value

Address

02

1

System Start/Stop

1 = Start 0 = Stop

10001

02

2

Op. Mode

1 = Auto 0 = Manual

10001

02

3

Analog Input #1 Failure

1 = Failure 0 = O.K.

10003

02

4

Analog Input #2 Failure

1 = Failure 0 = O.K.

10004

02

5

Analog Input #3 Failure

1 = Failure 0 = O.K.

10005

02

6

Analog Input #4 Failure

1 = Failure 0 = O.K.

10006

02

7

Analog Input #5 Failure

1 = Failure 0 = O.K.

10007

02

8

Analog Input #6 Failure

1 = Failure 0 = O.K.

10008

02

9

Analog Input #7 Failure

1 = Failure 0 = O.K.

10009

02

10

Analog Input #8 Failure

1 = Failure 0 = O.K.

10010

02

11

General Alarm

1 = Alarm 0 = O.K.

10019

05

1

System Start/Stop

1 = Start 0 = Stop

00001

05

2

System Purge

1 = Start Purge (positive edge)

00002

05

3

Summer/Winter

0 = Summer 1 = Winter

00003

04, 06

1

System Supply Temp

0 to Span

30001, 40001

04, 06

2

Zone Supply Temp

0 to Span

30002, 40002

04, 06

3

Zone Return Temp

0 to Span

30003, 40003

04, 06

4

Flow

0 to Span

30004, 40004

04, 06

5

Zone Supply Setpoint

0 to Span

30005, 40005

04, 06

6

Zone Return Setpoint

0 to Span

30006, 40006

04, 06

7

Active Process Variable

0 to Span

30007, 40007

04, 06

8

Active Setpoint

0 to Span

30008, 40008

04, 06

9

Valve Position

0 to 100%

30009, 40009

04, 06

10

Valve Feedback

0 to Span

30010, 40010

04, 06

11

Summer/Winter Mode

0 = disabled, 1 = Summer, 2 = Winter

30011, 40011