beautypg.com

Bell & Gossett S14333 Technologic 5500 Series ZoneSav Controller User Manual

Page 10

background image

10

3.2.1

Valve Position Limit

From the Valve Setup screen, shown in section 3.2,
Press 1 and ENTER to get to the Valve Position Limit
screen shown below.

Valve Pos. Limit

Minimum: ###%
Maximum: ###%

0% = Closed OK ? (Y/N)

Press YES and ENTER to accept the values and
return to the Valve Setup screen, shown in section
3.2, or press NO and ENTER to edit the fields. See
Table 6 for a description of the Valve Position Limit
variables.

Note: The minimum and maximum valve position lim-
its are ignored in manual operation mode.

3.2.2

Valve Log Rate

From the Valve Setup screen, shown in section 3.2,
Press 2 and ENTER to get to the Valve Log Rate
screen shown below.

Valve Log Rate: #
0=None

2=Hr

4=Week

1=Min

3=Day

5=Month
OK: ? (Y/N)

Press YES and ENTER to accept the current Valve
Log Rate, or press NO and ENTER to edit the Valve
Log Rate. See section 4.7.4 for more information on
the Valve Log. See Table 7 for a description of the
Valve Log Rate variables.

3.2.3

Valve Signal

From the Valve Setup screen, shown in section 3.2,
Press 3 and ENTER to get to the Valve Signal screen
shown below.

Valve Signal Type: #

1=4-20mA 2=0-10V

Signal Reversed: Y/N

OK: ? (Y/N)

Press YES and ENTER to accept the configuration
and return to the Valve Setup screen shown in sec-
tion 3.2. Press NO and ENTER to edit the fields. See
Table 8 for a description of the Valve Signal variables.

3.3

System Setup

From the Setup Selection screen, shown in section 3,
press the 3 and ENTER to get to the System Setup
screens shown below.

Selection: #

0 = Exit

1 = System Temp Limit
2 = PID
3 = Alarms

Press NEXT SCREEN key or PREV. SCREEN to view
neighboring screens. There are five screens in this
menu. The remaining screens are shown below.

Selection: #

0 = Exit

4 = Flow Limit
5 = System Purge
6 = Reset Totals

Selection: #

0 = Exit

7 = Date, Time
8 = Password
9 = I/O Setup

Selection: #

0 = Exit

10 = Communication
11 = Special Function
12 = Save to Flash

Selection: #

0 = Exit

13 = Load From Flash
14 = Set Contrast

Press the numeric key corresponding to the desired
System Setup sub-menu, and press ENTER.

Variable

Unit

Description

Default Value

Range

Field Value

Minimum

%

Minimum valve position in automatic operation mode

0

0-100

Maximum

%

Maximum valve position in automatic operation mode

100

0-100

Table 6: Valve Position Limit Variables

Variable

Description

Default Value

Range

Field Value

Valve Log Rate

One data point is taken at the end of the interval

0

0-5

Table 7: Valve Log Rate Variables

Variable

Description

Default Value

Range

Field Value

Valve Signal

Select 1 if the valve accepts a 4-20mA signal or select

1

1-2

Type

2 if it accepts a 0-10V signal

Signal Reversed

Select N if the valve is closed at 4mA or 0V. Select Y if

N

Y/N

the valve is open at 4mA or 0V

Table 8: Valve Signal Variables