beautypg.com

Bell & Gossett S14333 Technologic 5500 Series ZoneSav Controller User Manual

Page 11

background image

11

3.3.1

System Temperature Limit

From the System Setup Menu, shown in section 3.3,
press 1 and ENTER to get to the System Tempera-
ture Limit screen shown below.

System Temp Limit

Temp Limit = ###

Valve Opening = ###%

Timer = ###m OK ? (Y/N)

Press NO and ENTER to modify the fields, or press
YES and ENTER to exit back to accept the current
values and return to the System Setup screen, shown
in section 3.3. See Table 9 for a description of the
System Temperature Limit variables.

3.3.2

PID Setup

From the System Setup Menu, shown in section 3.3,
press 2 and ENTER to get to the PID Setup screen
shown below.

PID Selection: #
1 = Values

4 = AutoTune

2 = Index

5 = Optimize

3 = Heat/Cool

0 = Exit

Press the numeric key corresponding to the desired
PID Setup sub-menu, and press ENTER. Press 0 and
ENTER to return to the System Setup screen shown
in section 3.3.

3.3.2.1 PID Values

From the PID Setup screen, shown in section 3.3.2,
press 1 and ENTER to get to the PID Values screen
shown below.

(Type) PID VALUES
P = ###
I = ###
D = ###

Ok ? (Y/N)

There is a different set of values for the zone supply
temperature, zone return temperature and flow.
Press NEXT SCREEN or PREV. SCREEN to change
the type of analog input.

The user should contact B&G if assistance is needed
in tuning the ZoneSav Controller's gains. Also see
section 3.3.2.4 for Auto-Tuning. To edit the fields,
press NO and ENTER. Press YES and ENTER to
accept the values. See Table 10 for a description of
the PID values variables.

3.3.2.2 Setpoint Indexing

From the PID Setup screen, shown in section 3.3.2,
press 2 and ENTER to get to the Setpoint Indexing
screen shown below.

Setpoint Indexing
Sup Idx = #

ZSTmr = ## s

Ret Idx = #

ZRTmr = ## s
Ok ? (Y/N)

Variable

Unit

Description

Default Value

Range

Field Value

Temp

°F

If heating system, this is the low system temperature limit

55

0-999

Limit

If cooling system, this is the high system temperature limit

Valve

%

Valve opens to this position when system temperature

50

0-100

Opening

limit is exceeded

Timer

minutes

Valve will remain at the Valve Opening for the duration

1

0-99

of the timer

Table 9: System Temperature Limit Variables

Variable

Description

Default

Default

Default

Field

Field

Field

Range

Value

Value

Value

Value

Value

Value

(ZS)

(ZR)

(FL)

(ZS)

(ZR)

(FL)

Type

ZS = zone supply

N/A

N/A

N/A

N/A

N/A

N/A

N/A

ZR = zone return
FL = flow

PID-P

Proportional value

400

400

20

1-999

PID-I

Integral value

100

100

20

0-999

PID-D

Derivative value

0

0

0

0-999

Table 10: PID Values