Bell & Gossett S14333 Technologic 5500 Series ZoneSav Controller User Manual
Page 17

17
3.3.10.2 Metasys N2
From the Communication Setup Menu, shown in sec-
tion 3.3.10, press 2 and ENTER to get to the Metasys
N2 screen shown below.
Metasys N2
9600, 8, 1, 1, N. VND
Node = #
SP Ovrd: ? Y/N
Exit ? Y/N
The first line confirms setup for the Johnson Controls
N2 protocol. The second line defines the 9600 bps
baud rate, 8 bit data packets, 1 stop bit, 1 start bit
and no parity. To return to the Communications
Setup Menu, shown in section 3.3.10, press YES and
ENTER. To edit the fields, press NO and ENTER.
Table 25 gives a description of the Metasys N2
variables.
3.3.10.3 Modbus
From the Communication Setup Menu, shown in sec-
tion 3.3.10, press 3 and ENTER to get to the Modbus
screen shown below.
Modbus
9600, 8, 1, 1, N RTU
Node = #
SP Ovrd: ? Y/N
Exit ? Y/N
The first line confirms setup for Modbus protocol.
The second line defines the 9600 bps baud rate, 1
stop bit, 1 start bit, and no parity. To return to the
Communications Setup Menu, shown in section
3.3.10, press YES and ENTER. To edit the fields,
press NO/0 and ENTER. Table 26 gives a description
of the Modbus variables.
3.3.10.4 BACnet/IP
From the Communication Setup Menu, shown in sec-
tion 3.3.10, press 4 and ENTER to get to the
BACnet/IP screen shown below.
IP Address:
###. ###. ###. ###
Subnet:
###. ###. ###. ###
The BACnet device IP address and Subnet Mask are
provided by building management system. Press
NEXT SCREEN and the display will show:
Start Delay = ## Sec
Setpoint Ovrd: ?(Y/N)
Save IPAdd: ?(Y/N)
OK: ? (Y/N)
To return to the Communications Setup Menu, shown
in section 3.3.10, press YES and ENTER. To edit the
fields, press NO and ENTER. Table 27 gives a
description of the BACnet/IP variables.
For additional information concerning the above pro-
tocols, consult the Bell & Gossett Tech 500 Serial
Communications instruction manual (part number
S13654).
There may have been additional protocols added to
the communication setup menu, contact your Bell &
Gossett representative concerning additional proto-
cols and setups.
Variable
Description
Default Value
Range
Field Value
Node
Obtain the node number from the manufacturer that
1
0-255
supplied the device that will communicate with the
Technologic Controller
SP Ovrd
Select “Y” to allow the setpoints to be overwritten
N
Y/N
through the communications port
Table 25: Metasys N2 Variables
Variable
Description
Default Value
Range
Field Value
Node
Obtain the node number from the manufacturer that
1
255
supplied the device that will communicate with the
Technologic Controller
SP Ovrd
Select “Y” to allow the setpoints to be overwritten
N
Y/N
through the communications port
Table 26: Modbus Variables
Variable
Unit
Description
Default Value
Range
Field Value
Start Delay Seconds
Time delay to start the BACnet interface
10
0-999
Set Point
N/A
Select YES for the external device to override the local
N
Y/N
Ovrd
setpoint data
Save IP
N/A
Select YES to save IP address (restarts)
N
Y/N
Add
Table 27: BACnet/IP Variables