1 safety distances – GE Industrial Solutions GERAPID 2508, 4008, 5008, 6008 WITH ARC CHUTE 1X2 User Manual

Page 28

background image

28

Design and specifications are subject to change without notice

S47183De rev.02 2011-03-14

5.1 Safety distances.

Units call in mm (inches)



Legend for dimensional drawings

K

Heat sink (for Gerapid 6007)

L

Ventilation openings in the breaker cubicle top cover shall not be less than 50% of total surface area.

M

Solenoid closing drive

P

Diameter 9 mm [0,35 in], Countersunk screw M8

S

Control box

Z

Main Connector

Sa fety d istan ces - To Insu la ted Su rfa ces.

Unit s in mm (inch es)

Ty pe

Arc c hute

Main-

Addi tional

D eflect or

Gerapi d

Connecti on

is ol ation

E

A

B

C

D

2508 / 4008

1x2

H or V

10 (0.4)

700 (27.6)

150 (5.9)

150 (5.9)

120 (4.7)

5008

1x2

V / V with heat sinks

10 (0.4)

1000 (39.4)

300 (11.8)

300 (11.8)

180 (7.1)

6008

1x2

V / V with heat sinks

10 (0.4)

1000 (39.4)

300 (11.8)

300 (11.8)

180 (7.1)

H…Hor izontal term inal V...Vertical ter minal

Sa fety d istan ces - To Gr ounded Su rfac es .

Unit s in mm (inch es)

Ty pe

Arc c hute

Main-

Deflector

Gerapi d

Connecti on

E

A

B

C

D

2508 / 4008

1x2

H or V

10 (0.4)

1000 (39.4)

300 (11.8)

300 (11.8)

300 (11.8)

Safet y distan ces - Grounded Surfaces

Safety dist ances - Insulated Surfaces