GE Industrial Solutions GERAPID 2508, 4008, 5008, 6008 WITH ARC CHUTE 1X2 User Manual
Page 13

2011-03-14 S47183De rev.01
Design and specifications are subject to change without notice
13
3.4 Control circuits data
Control box terminals
1x12-pole
AC 400 V, 20 A
4x15-pole
AC 250 V, 8 A
Closing solenoid drive
1)
Rated voltage
AC 120 V, 230 V and DC 125 V, 250 V
Operating range
80 % - 115 % of rated voltage
Power consumption Gerapid 2508 / 4008
1750 W / 2000 W
Power consumption Gerapid 5008 / 6008
2600 W / 2600 W
Minimal CLOSING command duration
100 ms
min.interval between two "CLOSE" operations
~8 s w/o NEKO installed; ~14 s with NEKO
Internal voltage converter
1)
Input: Voltage range
DC 88 - 145 V
for Gerapid 2607, 4207, 6007, 8007
Output: Voltage range
DC 24 V (±5%)
Current
6 A permanent
Model description
PCMD 150 110 S24W-GE
Input: Voltage range
AC 115 - 240 V, DC 125 - 353 V
Output: Voltage range
DC 24 V (±5%)
Current
3 A permanent, 5 A/100 ms
Model description
PCMA 70 S24W-GE
Aux. contact HS 1…HS 8,
Rated operational voltage Ue/AC
230 V
OC trip target
Rated operational current Ie/AC-15
1 A
Arc chutes indicator
Conventional thermal current Ie/AC-12 (Ith)
10 A
Rated operational voltage Ue/DC
110 V / 220 V
Rated operational current Ie/DC-13
0.5 A / 0.3 A
Minimum current/voltage ratings
0,1 mA / 6 V DC
Contact duty (min. value)
DC 10 V / 2 mA
Shunt trip standard
Rated voltage/power Uc/Pc
24 V / 100 W
Operating range: OFF
21.6 V - 26.4 V
Shunt trip double winded
Rated voltage/power Uc
DC 125 V/ DC 220 V
Rated power for a single winding Pc
230 W
UVR
Rated voltage Uc
24 V
(Zero voltage release)
Operating range: OFF
< 4 V
Operating range: ON
24 V (±10%)
Power consumption
~ 10 W
ED impulse release
Required C-bank capacity
2000 µF
Charging voltage
300 V
Switching interval
max. 2/min with 10 consecutive operations
Endurance
1 000 operations with 1 operation per 180 s
Firing signal level / duration
6 - 24 V / 100 - 1000 ms
Charging signalization relay AC duty AC 250 V/ 0.5 A - AC 120 V /1 A
DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A
1)
Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please call back.
Table 2a: Technical data of auxiliary circuits
Components
Technical datas of control circuits
Us / In
SU-Control
CLOSE-push-button -S1
DC 24 V / approx. 10 mA
ST releasing
push-button-S2
DC 24 V / approx. 4 A short time
UVR releasing
push-button -S2 ( -X2 :6 / :7)
DC 24 V / approx. 10 mA
push-button -S2 ( -X2 :8 / :9 )
DC 24 V / approx. 450 mA
ED-coil tripping w/o NEKO
push-button -S3
DC 300 V / 750 A / 3 ms
ED-coil tripping with NEKO
Connect "Firing signal" at ( -X2 :10 / :11 )
DC 6 V…24 V / approx.20 mA
Table 2b: Control circuits ( directional values to rate the components )