2 dual input utility (option) – GE Industrial Solutions LP 33 Series 30 & 40 kVA Installation Guide User Manual
Page 29

Modifications reserved
Page 29/41
OPM_LPS_3UI_30K_40K_0US_V010.doc
Installation Guide LP 33 Series 10-20 kVA
3.9.2
Dual input utility (option)
Fig. 3.9.2-1 Dual input utility (option)
Dual input utility
On request, the UPS can be delivered for dual input
utility.
Two independent lines (F2 and F3) supply separately
the rectifier and the bypass inputs
With this configuration, when the rectifier-input fuses
are opened, the automatic bypass and the
maintenance bypass are supplied by the other line.
LPS33U_
030-040_
Connectio
n separat
e_02US
Utility 1
X4
Battery
Load
X1
X3
L1-1
L2
-1
L3-
1
N1
PE
L1
L2
L3
N2
PE
-
0
+
PE
Utility 2
X2
L1
-2
L2-
2
L3-2
N
Fig. 3.9.2-2 Terminals for dual input utility
X1 Mains 1 - Rectifier input utility connection
L1-1 = Rectifier Phase A
L2-1 = Rectifier Phase B
L3-1 = Rectifier Phase C
N1 =
Mains
Neutral
PE =
Main
Ground
X2 Mains 2 - Bypass input utility connection
L1-2 = Bypass Phase A
L2-2 = Bypass Phase B
L3-2 = Bypass Phase C
N =
Mains
Neutral
X3 Load - Output load connection
L1 = Load
Phase
A
L2 = Load
Phase
B
L3 = Load
Phase
C
N2 =
Load
Neutral
PE = Load Ground
Connect wire to the terminals by using
appropriate tools and appropriate torque.
Torque specification for Input / Output and DC
power connections on Terminals: Section 3.8.1.
LP 33 Series / 30 kVA
1 AWG (35mm
2
)
Max. rating X1, X2 , X3 and X4 terminals:
LP 33 Series / 40 kVA
4/0 AWG (95mm
2
)
NOTE !
For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1 and N2 are connected together.
NOTE !
This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.