How to access the terminals for the cable connections
LPS33U_
030-040_
Connecti
on_01US
OFF
ON
OFF
ON
Bottom entry cables
C
B
A
C
Fig. 3.8.1-1 Access to the input / output connections
To access input, output and battery connections
proceed as follows:
• Open the front door “A” of the cabinet.
• Remove the protection panel “B”.
• Remove the plate “C” for bottom cable entry.
NOTE !
Drill in the plate “C” appropriate holes for cable conduits (max. 4 x 2”).
See Fig 3.8.1-1 for details “C”.
3.8.2 Internal
fuse
ratings
LP 33 Series internal fuses
The UPS is equipped with battery
fuses F5, F6, F7.
In case of replacement the same
type and the same rating must be
used (see table below).
LPS33U_030-040
_F5-F6-F7_01
OFF
ON
OFF
ON
F7
F5
F6
Fig. 3.8.2-1 Battery fuses F5 – F6 – F7
WARNING !
The replacement of
battery fuses must
be performed by
QUALIFIED SERVICE
PERSONNEL only.
UPS
Battery fuses F5 – F6 – F7
LP 33 Series / 30 kVA
Fuse NH00 125A UL recognized
LP 33 Series / 40 kVA
Fuse NH00 160A UL recognized