beautypg.com

8 wiring connection – GE Industrial Solutions LP 33 Series 30 & 40 kVA Installation Guide User Manual

Page 26

background image

Modifications reserved

Page 26/41

OPM_LPS_3UI_30K_40K_0US_V010.doc

Installation Guide LP 33 Series 10-20 kVA

3.8 WIRING

CONNECTION

WARNING!

UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.


3.8.1 Power

connections

Input/output and DC connections are provided with terminal blocks.

Please refer to chart for torque specifications.

Carefully read the following recommendations before proceeding:

Ensure that the AC and DC external isolators are OFF and locked to prevent their inadvertent
operation.

Do not close any external isolators prior the commissioning of the equipment.

The preferred power cable entry location for installation purposes is from the bottom right side of
the UPS.
In case of cable entry from the top of the cabinet, remove the cover plate fitted on the roof and

provide for a suitable isolated protection cover.

In case of cable entry from the bottom remove cover plate and perform the same procedure.

The input/output cables must be connected in clockwise phase rotation for both Bypass and
Rectifier Input Terminals if separate, taking care to avoid risk of short circuit between different

poles.

The grounding and neutral connection of the electrical system must be in accordance with local

regulations.

In case of additional cabinets containing batteries, input/ output transformers, etc, their ground

terminals must be connected to the UPS main ground terminal.

Once the power cables have been connected, re-install the internal safety shields and close the

cabinets by re-installing all external panels.


Torque Specifications

Mechanical Terminals

Input / Output / Battery and GND

UPS Model

WIRE SIZE RANGE

Lb - in

Nm

LP 33 Series / 30 kVA

Max 1 AWG

33.2

3.8

LP 33 Series / 40 kVA

Max 4/0 AWG

50

5.7