7 testing and certification – GE Industrial Solutions EntelliPro ES User Manual
Page 22

CHAPTER 1: INTR ODUCTION
1.14
EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
1.2.7 Testing and certification
Test Reference Standard Test Level
Dielectric voltage withstands ...................................
.......1.5kV
Impulse voltage withstand ..............................................EN60255-5
Electrostatic discharge.......................................................EN61000-4-2/IEC60255-22-2 Level 4
RF immunity ............................................................................EN61000-4-3/IEC60255-22-3 Level 3
Fast transient disturbance ...............................................EN61000-4-4/IEC60255-22-4 Class A
Surge immunity ................. ..................................................EN61000-4-5/IEC60255-22-5 Level 3
Conducted RF immunity ....................................................EN61000-4-6/IEC60255-22-6 Level 3
Radiated and conducted emissions.............................CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal vibration ...........................................................IEC60255-21-1 Class 1
Voltage dip and interruption ..........................................IEC61000-4-11 0, 40, 70% dips, 250/300 cycle interrupts
Harmonics ..................................................................
............IEC61000-4-13
Voltage ripple ........................................................................IEC61000-4-17 15% ripple
Environmental (cold)................................................. .........IEC60068-2-1 -25° C,
96 hrs
Environmental (dry heat) .................................................IEC60068- 2-2 70° C,
96 hrs
Relative humidity cyclic ...................................................IEC60068- 2-30 6-day variant 2
Short-circuit current*.........................................................IEC60947-5-1
ATEX certificati
o
Rated impulse withstand voltage ............................4kV
(when EntelliPro ES is not directly connected to the main voltage)
(when EntelliPro ES is directly connected to the main voltage)
Overvoltage category II according to IEC 60947-1 7.2.3.1 item 2) b)
Pollution degree...................................................................I
Overvoltage category III according to IEC 60947-1 7.2.3.1 item 2) b)
SIL1
Profibus certification
*CAUTION:
A maximum A7DQS or gl 10A fuse is required on motor relays.
Pper