When starting the EntelliPro ES using Profibus-DP, the Profibus Class1 (PB-C1) master sends parameters to the EntelliPro ES
device. This Profibus-DP Set_Param service can also include device-specific parameters, to change the EntelliPro behavior.
These specific parameters can be adjusted in the PB-Class1 master configurator software tool. For this the EntelliPro ES GSD
file is needed. It is part of the documentation CD.
The Profibus-DP Class1 parameterizing (Profibus-DP service “Set_Param” from standard) is shown witht he PB configuration
tools
www.Hilscher.com
Each PB-C1 master device has a similar Configuration Tool to install the cyclic parameterization and configuration values.
The Profibus-DP Class1 parameterization is deactivated in the presetting of the Profibus-DP GSD file.
If you use the EntelliPro ES to protect the motor
in potentially explosive atmospheres (ATEX) it’s mandatory
to set the ATEX relevant parameters to the required value. See ATEX configuration in chapter 2.2.1.6.
Figure below shows the SYCon main window. The SyCon main window shows the master and slave configuration (device
name, device address and device type) of the Profibus-DP line.
Right-hand mouse key for
the parameterization.