GE Industrial Solutions Spectra RMS Molded Case User Manual
Page 41

40
GEH-702 Users Manual
Table 28. Communication Parameters: Modbus Function 4
Register
Parameter Name
Allowable Values
Read/Write
14
Power Peak Demand Total - Lo 16 bits
32 bit
Read
15
Power Peak Demand Total - Hi 16 bits
Read
18
Voltage Phase A
16 bit
Read
19
Voltage Phase B
16 bit
Read
20
Voltage Phase C
16 bit
Read
21
Current Phase A
16 bit
Read
23
Current Phase B
16 bit
Read
25
Current Phase C
16 bit
Read
27
Current Phase N
16 bit
Read
29
Rating Plug Value
0
60
80
100
125
150
200
225
250
300
350
400
450
500
600
700
750
800
900
1000
1100
1200
Read
31
Energy Total ( 0-15 bits )
16 bit
Read
32
Energy Total (16-31 bits)
16 bit
Read
35
Energy Rollover Count
16 bit
Read
36
Power Factor Phase A
16 bit
Read
37
Power Factor Phase B
16 bit
Read
38
Power Factor Phase C
16 bit
Read
39
Power Factor Total
16 bit
Read
40
Power Real Phase A - Lo 16 bits
32 bit
Read
41
Power Real Phase A - Hi 16 bits
Read
42
Power Real Phase B - Lo 16 bits
32 bit
Read
43
Power Real Phase B - Hi 16 bits
Read
44
Power Real Phase C - Lo 16 bits
32 bit
Read
45
Power Real Phase C - Hi 16 bits
Read
46
Power Real Phase Total - Lo 16 bits
32 bit
Read
47
Power Real Phase Total - Hi 16 bits
Read
48
Power Reactive Phase A - Lo 16 bits
32 bit
Read
49
Power Reactive Phase A - Hi 16 bits
Read
50
Power Reactive Phase B - Lo 16 bits
32 bit
Read