beautypg.com

VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 67

background image

VEGADIF

55

is used in all versions for level measurement in closed

vessels.

Note:
VEGADIF

55

in cell isolating diaphragm version is immediately ready

for operation.

VEGADIF

55

in flange version: After opening a probably existing block

valve, the instrument is ready for operation.

B

efore you adjust VEGADIF 55 in basic version, you have to clean the

effective pressure lines and the instrument must be filled with the

medium.

+

A

B

6

7

3

2

4

1

5

+

II

I

III

III

Fig. 67: Closed vessel with steam layer
I

VEGADIF 55

II

Three-fold valve block

III

Precipitator

1

, 5 Drain valves

2

, 4 Inlet valves

3

Breather valve

6

, 7 Vent valves on VEGADIF 55

A, B Block valves

P

roceed as follows to prepare the actual adjustment:

1

F

ill the vessel to just above the lower tap

2

F

ill measuring system with medium

O

pen valve A and B: Open block valves

Vessel with steam layer-
ing

VEGADIF

55 • 4 … 20

mA/HART

67

7 S

et up

31731

-EN

-081119