VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 38
1
P
ressure for LRV is on the instrument
2
P
ush "-" key at least for 3 s
3
D
oes the LED on the electronics module light briefly?
Y
es: existing pressure was accepted as LRV
N
o: Existing pressure for LRV was not accepted, note the
adjustment limits
Set URV:
1
P
ressure for URV is on the instrument
2
P
ush "+" key at least for 3 s
3
D
oes the LED on the electronics module light briefly?
Y
es: existing pressure was accepted as URV
N
o: existing pressure for URV was not accepted, take note of the
adjustment limits
I
f no local indication is connected, the following functions will be
possible via the three keys on the electronics module or outside on the
instrument:
l
P
osition adjustment (zero point correction)
l
S
et the lower and upper pressure value and assign a level value to
the lower or upper level value
l
I
nstrument reset, see chart in chapter "Operating elements"
Information:
T
he adjustment must be unlocked, see chapter "Lock/Unlock adjust-
ment".
B
y default, the instrument is set to mode Pressure. The mode can be
changed via the parameter "Measuring Mode", see chapter "Select
language and measuring mode".
I
f "Level Mode" "Pressure Linearized" or "Height Linearized" or
"
Calibration Mode" "dry"
are selected, the "-" and "+" keys are without
function.
T
he existing pressure must be within the nominal pressure limits of the
sensor, see specifications on the "Type label".
S
ee also "Quick setup menu" in chapter "Level measurement"
l
D
efault settings of the parameters in mode "Level":
-
LEVEL MODE = L
inear
-
CALIBRATION MODE =
wet
-
LIN. MEASURAND = %
-
EMPTY CALIB. = 0 %
-
FULL CALIB. = 100 %
Carry out position adjustment:
1
P
ressure on the instrument
2
P
ush "E" key at least for 3 s
Measuring Mode - Level
38
VEGADIF
55 • 4 … 20
mA/HART
6 O
peration
31731
-EN
-081119