à Mount VEGADIF 55 below the measurement loop so that the

effective pressure lines are always filled with liquid and gas

bubbles can bubble up to the process line

à For measurements in products with solid content such as e.g. dirty

liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.

+

1

4

2

2

3

Fig. 17: Measurement setup, differential pressure measurement in gases,
vapours and liquids with VEGADIF 55
1

Cell isolating diaphragm

2

Capillaries

3

E.g. filter

4

VEGADIF 55

à Mount isolating diaphragm with capillaries on top or laterally on the

pipeline

à In vacuum applications: Mount VEGADIF 55 below the measure-

ment loop

à The ambient temperature should be the same for both capillaries

4

.5 Mounting for instruments with isolating

diaphragms

Isolating diaphragm
N

ote these general instructions to the isolating diaphragms:

Note:

l

A

n isolating diaphragm together with a pressure transmitter forms

a closed, calibrated system which is filled through openings in the

isolating diaphragm and the measuring element of the pressure
transmitter. These openings are sealed and must not be opened!

l

D

o not clean or touch the isolating diaphragm with hard or sharp

subjects

l

R

emove the diaphragm protection just before installation

l

W

hen using a mounting strap, there must be sufficient strain relief

for the capillaries to avoid bending them (bending radius ≥ 100 mm)

Differential pressure
measurement in gases,
vapours and liquids

VEGADIF

55 • 4 … 20

mA/HART

21

4 M

ounting