VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 50
which can be reset by the respective reset code. To carry out a reset,
the adjustment must be unlocked (see chapter "Lock/Unlock adjust-
ment").
Information:
C
ustomer-specific parameter adjustments (default) remain even after
a reset. If you want that the parameters are reset to default, you have
to contact VEGA.
Reset code
Description
1846
Indication Reset
l This reset resets all parameters relating to the display (DISPLAY Group)
l If a simulation is running, this will be terminated
l The instrument carries out a restart
62
PowerUp reset (warm start)
l This reset resets all parameters in the RAM. Data are reread from the EEPROM (processor is
re-initialised)
l If a simulation is running, this will be terminated
l The instrument carries out a restart
2710
Reset mode level
l Depending on the settings of the parameters LEVEL MODE and LIN MEASURAND, LINd
MEASURAND
or COMB. MEASURAND all parameters necessary for this application are reset.
l If a simulation is running, this will be terminated
l The instrument carries out a restart
333
User reset
T
his reset resets the following parameters:
l Function group POSITION ADJUSTMENT
l Function group BASIC SETUP, except the customer-specific units
l Function group EXT. SETUP
l Function group: TOTALIZER SETUP
l Group OUTPUT
l Function group HART DATA: BUS ADDRESS and PREAMBLE NUMBER
l If a simulation is running, this will be terminated
l The instrument carries out a restart
50
VEGADIF
55 • 4 … 20
mA/HART
6 O
peration
31731
-EN
-081119