beautypg.com

VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 50

background image

which can be reset by the respective reset code. To carry out a reset,
the adjustment must be unlocked (see chapter "Lock/Unlock adjust-
ment
").

Information:
C

ustomer-specific parameter adjustments (default) remain even after

a reset. If you want that the parameters are reset to default, you have
to contact VEGA.

Reset code

Description

1846

Indication Reset

l This reset resets all parameters relating to the display (DISPLAY Group)
l If a simulation is running, this will be terminated
l The instrument carries out a restart

62

PowerUp reset (warm start)

l This reset resets all parameters in the RAM. Data are reread from the EEPROM (processor is

re-initialised)

l If a simulation is running, this will be terminated
l The instrument carries out a restart

2710

Reset mode level

l Depending on the settings of the parameters LEVEL MODE and LIN MEASURAND, LINd

MEASURAND

or COMB. MEASURAND all parameters necessary for this application are reset.

l If a simulation is running, this will be terminated
l The instrument carries out a restart

333

User reset
T

his reset resets the following parameters:

l Function group POSITION ADJUSTMENT
l Function group BASIC SETUP, except the customer-specific units
l Function group EXT. SETUP
l Function group: TOTALIZER SETUP
l Group OUTPUT
l Function group HART DATA: BUS ADDRESS and PREAMBLE NUMBER
l If a simulation is running, this will be terminated
l The instrument carries out a restart

50

VEGADIF

55 • 4 … 20

mA/HART

6 O

peration

31731

-EN

-081119