MAX FLOW
MAX. PRESS. FLOW
DAMPING VALUE
POS. ZERO ADJUST
MEASURING MODE
OPERATING MENU
QUICK SETUP
Measured value
LANGUAGE
GROUP SELECTION
Flow
Pressure
Level
MEASURING MODE
1
Indication only via local indication
2
Indication only via HART handheld
Measured value indication: M
ove with "E" from the measured value
presentation to the GROUP SELECTION.
GROUP SELECTION: S
elect parameter MEASURING MODE.
MEASURING MODE: S
elect option "Flow".
GROUP SELECTION: S
elect Quick SETUP menu.
POS. ZERO ADJUST: D
ue due the installation position of the
instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE
via the parameter POS. ZERO ADJUST with the
option "Accept", i.e. assign the value 0 to the existing pressure.
MAX. FLOW: E
nter the max. flow of the effective pressure transmitter
(
see also construction sheet of the effective pressure transmitter).
MAX. PRESSURE: E
nter the max. pressure of the effective pressure
transmitter (see also construction sheet of the effective pressure
transmitter).
DAMPING VALUE: E
nter the damping time (time constant τ). The
damping influences the speed with which all following elements such
as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).