VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 47

Information:
T
he adjustment must be unlocked. See also chapter "Lock/Unlock
adjustment".
1
S
eparate instrument from voltage supply
2
P
lug the data memory module into the electronics module.
C
onfiguration data of a different instrument are saved in the data
memory module.
3
C
onnect instrument again to voltage supply
4
Y
ou select via the parameter DOWNLOAD SELECT which
parameter should be overwritten (menu path: "Group selection -
Operating menu - Operating")
D
epending on the selection, the following parameters are over-
written:
Copy config.: All parameters except DEVICE SERIAL NO.,
DEVICE DESIGN., CUST. TAG NUMBER, LONG TAG NUMBER,
DESCRIPTION, BUS ADDRESS
and the parameters of group
POSITION ADJUSTMENT
and PROCESS CONNECTION.
Instrument change: A
ll parameters except DEVICE SERIAL NO.,
DEVICE DESIGN.
and the parameters of group POSITION
ADJUSTMENT
and PROCESS CONNECTION
Electronics exchange: A
ll parameters except the parameters of
group POSITION ADJUSTMENT. Factory setting: Copy config.
5
S
elect via the parameter HistoROM CONTROL the option
"
HistoROM - Instrument"
for the transmission direction (menu
path: "Group selection - Operating menu - Operating").
6
W
ait approx. 20 sec. Configuration data are loaded from the data
memory module to the instrument. The instrument carries out a
restart.
7
B
efore you remove the data memory module from the electronics
module, you have to separate the instrument from the voltage
supply