2 connection procedure, 3 wiring plan – VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 28
5
.2 Connection procedure
P
roceed as follows:
1
U
nscrew the housing cover
2
L
oosen compression nut of the cable entry
3
R
emove approx. 10 cm (4 in) of the cable mantle, strip approx.
1
cm (0.4 in) insulation from the ends of the individual wires
4
I
nsert the cable through the cable gland into the sensor
5
L
oosen the screws on the terminals
6
I
nsert the wire ends into the open terminals according to the wiring
plan
7
T
ighten the screws of the terminals
8
C
heck the hold of the wires in the terminals by lightly pulling on
them
9
C
onnect the screen to the internal ground terminal, connect the
outer ground terminal with potential equalisation
10 T
ighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
11 S
crew the housing cover on
T
he electrical connection is finished.
5
.3 Wiring plan
Test
Test
4... 20mA
5
4
3
2
1
Fig. 24: Housing overview, view to the connection compartment
1
Housing
2
Bridge for 4 … 20 mA test signal
3
Internal ground terminal
4
External ground terminal
5
4
… 20 mA test signal between plus and test terminal
Housing overview
28
VEGADIF
55 • 4 … 20
mA/HART
5 C
onnecting to power supply
31731
-EN
-081119