VEGA VEGACOM 558 Ethernet User Manual
Page 6
![background image](/manuals/261076/6/background.png)
6
VEGACOM 558 Ethernet
Ethernet interface on the front plate (mode 10BaseT)
Interface standard
Ethernet (IEEE802.3)
Line impedance
100 Ohm +/– 15 %
Cable type
Ethernet-Patch cable category 5 (STP)
Wire cross-section
0.2 mm
2
No. of wires
4
Max. transmission rate
10 Mbits/s
Coding
Manchester
Topology
star
Max. segment length
100 m
Plug version
8-pole RJ45 plug
Frame-Format
Ethernet Version 2
Ethernet interface on the front plate (mode 100BaseTX/Fast Ethernet)
Interface standard
Ethernet (IEEE802.3)
Line impedance
100 Ohm +/– 15 %
Cable type
Ethernet-Patch cable category 5 (STP)
Wire cross-section
0.2 mm
2
No. of wires
4
Max. transmission rate
100 Mbits/s
Coding
Manchester with 4B/5B procedure
Topology
star
Max. segment length
100 m
Plug version
8-pole RJ45 plug
Frame-Format
Ethernet Version 2
Electrical protective measures
Protection
- not mounted
IP 00
- in carrier BGT596
or BGT LOG571
- front side completely equipped
IP 40
- upper and lower side
BGT596
IP 00
BGT LOG571
IP 20
- wiring side
IP 00
- in housing type 505
- front side
IP 40
- other sides
IP 30
Protection class
II (in housing type 505)
Overvoltage category
II
Electrical separating measures
Reliable separation acc. to VDE 0106, part 1 between power supply, LOGBUS, DISBUS,
RS 232 and Ethernet
- reference voltage
250 V
- test voltage
2 kV
Product description