3 technical data – VEGA VEGACOM 558 Ethernet User Manual
Page 5
![background image](/manuals/261076/5/background.png)
VEGACOM 558 Ethernet
5
Product description
1.3 Technical data
Power supply
Operating voltage
U
nom
= 24 V AC (20 … 53 V), 50/60 Hz or
= 24 V DC (20 … 72 V)
Power consumption
approx. 4 VA
Fuse
1 A, slow-blow
Electrical connection
Component
multiple plug acc. to DIN 41 612, series F
48-pole (d, b, z) with coding holes
Module in carrier
BGT 596 or BGT LOG571
suitable multipoint connector acc. to DIN 41 612
with connection via standard technologies
Housing type 505
via screw terminals max. 1 x 1.5 mm
2
Indicating elements
LEDs in front plate
- on (green)
operating condition
- ! (red)
failure indication
- Ethernet (green/red)
status Ethernet (linked, TX, RX)
- 1 (green/red)
save indication
- 2 (green/red)
status LOGBUS
- 3 (green/red)
status DISBUS
Measured data input DISBUS
Data transmission
DISBUS (digital data transmission)
Connection cable
connection via 48-pole multipoint connector
2-wire standard cable (screened)
Max. cable length
1000 m
Measured data input LOGBUS
Data transmission
LOGBUS (digital data transmission)
Connection cable
connection via bus plug
RS 232 interface on front plate
Interface standard
RS 232C
Cable length
max. 15 m
Transmission rate in baud
9600, 19200, 38400, 57600
Transmission format
8 data bits, 1 stop bit, no parity
Plug in the front plate
SUB-D plug connector, 9-pole, pins