VEGA VEGACOM 557 Modbus protocol User Manual
Page 39

VEGACOM 557 Modbus
39
Data transmission with Modbus RTU
Start
Slave
ad-
dress
Func-
tion
code
Address of
1. register bit
Number of
register
bits
Error
Check
End
Number
of Bytes
Value
range
Meaning
Structure of the enquiry acc. to switching status from Modbus-Master to VEGACOM 557
RTU enquiry telegram acc. to switching conditions (function code 01)
3 ... 4
1
1
2
2
2
3 ... 4
Closed level
1 .. 247
01
0 ... 65.509
8 ... 2.040
CRC
Closed level
0x01
0x01
0x00
0x20
0x00
0x20
0xXX
0xXX
Start
Slave
ad-
dress
Func-
tion-
code
No. of
data
bytes
Error
Check
End
No. of
Bytes
Value
range
Meaning
Structure of the answer VEGACOM 557 to Modbus-Master
RTU answer telegram (function code 01)
3 ... 4
1
1
1
1 byte for 8
register bits
2
3 ... 4
Closed level
1 .. 247
01
255
1 ... 127
CRC
Closed level
0x01
0x01
0x04
0x00
0x0F
0x00
0x0F
0xXX
Data (switching status)
0xXX
Switching status to
AR card #4
Switching status to
AR card #3