VEGACOM 557 Modbus

39

Data transmission with Modbus RTU

Start

Slave

ad-

dress

Func-

tion

code

Address of

1. register bit

Number of

register

bits

Error

Check

End

Number

of Bytes

Value

range

Meaning

Structure of the enquiry acc. to switching status from Modbus-Master to VEGACOM 557

RTU enquiry telegram acc. to switching conditions (function code 01)

3 ... 4

1

1

2

2

2

3 ... 4

Closed level

1 .. 247

01

0 ... 65.509

8 ... 2.040

CRC

Closed level

0x01

0x01

0x00

0x20

0x00

0x20

0xXX

0xXX

Start

Slave

ad-

dress

Func-

tion-

code

No. of

data

bytes

Error

Check

End

No. of

Bytes

Value

range

Meaning

Structure of the answer VEGACOM 557 to Modbus-Master

RTU answer telegram (function code 01)

3 ... 4

1

1

1

1 byte for 8

register bits

2

3 ... 4

Closed level

1 .. 247

01

255

1 ... 127

CRC

Closed level

0x01

0x01

0x04

0x00

0x0F

0x00

0x0F

0xXX

Data (switching status)

0xXX

Switching status to
AR card #4

Switching status to
AR card #3