VEGACOM 557 Modbus

11

Product description

Modbus RTU-mode

Coding system

8 bits binary, hexadecimal

Number of bits

1 start bit, 8 data bits, 1 (0) parity bit,
1 stop bit

Parity

NONE, ODD, EVEN

Backup

CRC - 16

Modbus ASCII-mode

Coding system

hexadecimal, ASCII-character

Number of bits

1 start bit, 8 (7) data bits, 1 (0) parity bit,
1 stop bit

Parity

NONE, ODD, EVEN

Backup

LRC

Electrical protective measures

Protection:
not mounted

IP 00

in carrier BGT 596
or BGT LOG 571
- front side completely equipped

IP 40

- upper and lower side

BGT 596

IP 00

BGT LOG 571

IP 20

- wiring side

IP 00

in housing type 505
- front side

IP 40

- other sides

IP 30

Protection class

II (in housing type 505)

Overvoltage category

II

Electrical separation measures

Reliable separation acc. to VDE 0106, part 1 between power supply, LOGBUS, DISBUS,
PC-connection and respective interface
- reference voltage

250 V

- test voltage

2 kV

CE conformity

VEGACOM 557 meets the protective regulations of EMC (89/336/EWG) and NSR
(73/23/EWG). The conformity has been judged acc. to the following standards:
EMC

Emission

EN 50 081 - 2: 1993

Susceptibility

EN 50 082 - 2: 1995

NSR

EN 61 010 - 1: 1993